VA4
Bristow, VA
Acquired in 2005 as a fully developed data center, VA4 is situated on 32 acres of land in Prince William County, Virginia. The facility comprises approximately 230,000 gross square feet and 90,000 raised square feet divided into six computer rooms with an aggregate critical load of 9.6 MW, with 3.0 MW available to each of two pairs of computer rooms and 3.6 MW available to a third pair of computer rooms. As of August 1, 2007, VA4 was 100% leased.
Specifications
| Property | |
|---|---|
| Location | Bristow, VA |
| Completed | 2002 |
| Acreage | 37.7 |
| Building Size (sq ft) | 232,000 |
| Nearest Airport | 23 miles from Dulles International Airport and 7 miles from Manassas Airport |
| Critical Power | |
| Total MW | 9.6 |
| Building Description | |
| Parking | 167 |
| # of Stories | 1 |
| Loading Area and Docks | 9 Loading Bays |
| Elevators | No |
| Ceiling Height | 18 ft |
| Data Center Area Description | |
| Raised Floor Area | 90,000 |
| # of Quadrants | 6 |
| Raised Floor Height | 24" |
| UPS Systems | |
| Description | (3) 3600-kW Static UPS Systems. Backed up by (1) 3900-kW Rotary UPS System. |
| Redundancy | N+2 |
| Generators | |
| Description | 10 diesel-powered emergency generators with 2,000 kW capacity |
| Redundancy | N+2 |
| Utility Power | |
| NOVEC - Direct Substation Feed - 24.9 kV | |
| Heat Rejection systems (AC) | |
| Description | Water cooled chilled water cooling system, capacity 5400 Tons |
| Redundancy | N+2 |
| On site Fuel | |
| # of Gallons | 160,000 gallon underground diesel storage tanks |
| # of Hours | 72 Hours |
| Fire Protection | |
| Extensive dry pipe, zoned, pre-action fire protection system | |
| Security | |
| Building and Perimeter | Double gate secured entrances and fully fenced perimeter |
| Space Security | Staffed 24/7 with separate security lobby |
| Access Control | Electronic Security features with card key access |
| Alarm System | Yes |
| CCTV | Camera Surveillance |
| PDUs | |
| 300-kVA 600 Volt Primary power distribution units | |
| 225-A 208 volt static transfer switches | |
| Tenant Office Space | |
| Available | |
| Communications | |
| Multiple carriers available | |
| Expansion Potential | |
| Yes | |