Dupont Fabros Technology

Contact Us

(202) 728-0044
 
 
View Larger
  • Building (east side)
Photos Documents Stats

Specifications

Property
Location Reston, VA
Completed 2001
Acreage 10.01
Building Size (sq ft) 256,000
Nearest Airport 7.2 Miles from Dulles International Airport
Critical Power
Total MW 13
Building Description
Parking 175
# of Stories 3 plus penthouse
Loading Area and Docks   2 Loading Bays
Elevators 1 Freight elevator and 1 passenger elevator
Ceiling Height 14 ft
Data Center Area Description
Raised Floor Area 144,900
# of Quadrants 8
Raised Floor Height 30"
UPS Systems
Description 12 Rotary power systems with 1300 kW of critical output
Redundancy N+2
Generators
Description 18 diesel-powered emergency generators with 2000 kW capacity
Redundancy N+2
Utility Power
  Dominion Virginia Power - 34.5 kV
Heat Rejection systems (AC)
Description Water cooled chilled water cooling system, capacity 5820 Tons
Redundancy N+2
On site Fuel
# of Gallons 3 x 40,000 gallon underground diesel storage tanks
# of Hours Nominal 60 Hours
Fire Protection
  Laser based Very Early Smoke Detection (VESDA) and a pre-action zoned dry-pipe system
Security
Building and Perimeter Bullet resistant security check-in
Space Security Staffed 24/7 with separate security lobby
Access Control Electronic Security features with card key access
Alarm System Yes
CCTV Camera Surveillance through 170 perimeter cameras with archive
PDUs
  200-kVA Power Distribution Units with Integral Static Transfer Switches
Tenant Office Space
  Available
Communications
  * 2 redundant and diverse POE for Carriers with no single point of cable plant failure
  * 7 carriers available
Expansion Potential
  Yes
.