Dupont Fabros Technology

Contact Us

(202) 728-0044
 
 
View Larger
  • Building Front
Photos Documents Stats

Specifications

Property
Location Ashburn, VA
Completed 2006
Acreage 9.74
Building Size (sq ft) 147,000
Nearest Airport 7 Miles from Dulles International Airport
Critical Power
Total MW 13
Building Description
Parking 213
# of Stories 1
Loading Area and Docks   2 Loading Bays
Elevators No
Ceiling Height 10 ft
Data Center Area Description
Raised Floor Area 79,600
# of Quadrants 4
Raised Floor Height 42"
UPS Systems
Description 12 Rotary power systems with 1,300 kW of critical output, 500 kW of essential output
Redundancy N+2 redundancy
Generators
Description 5 diesel-powered emergency generators with 2,000 kW capacity
Redundancy N+2
Utility Power
  Dominion Virginia Power - 34.5 kV
Heat Rejection systems (AC)
Description Water cooled chilled water cooling system, capacity 7,200 Tons
Redundancy N+2
On site Fuel
# of Gallons 100,000 gallons
# of Hours Nominal 55 Hours
Fire Protection
  Extensive pre-action zoned dry-pipe fire protection system with subfloor, room, and above ceiling smoke detectors
Security
Building and Perimeter Bullet resistant protection at security check-in, front window areas and loading dock
Space Security Staffed 24/7 with separate security lobby
Access Control Electronic Security features with card key access
Alarm System Yes
CCTV Camera Surveillance
PDUs
  300-kVA Power Distribution Units with Integral Static Transfer Switches
Tenant Office Space
  Available
Communications
  * 2 redundant and diverse POE for Carriers with no single point of cable plant failure
Expansion Potential
  No
.